thermal: gov_bang_bang: Relocate regulation logic description
Move the regulation logic description from the bang_bang_trip_crossed() kerneldoc to the preamble. No functional impact. Signed-off-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com> Reviewed-by: Lukasz Luba <lukasz.luba@arm.com> Link: https://patch.msgid.link/4987649.31r3eYUQgx@rjwysocki.net [ rjw: Removed a trailing whitespace ] Signed-off-by: Rafael J. Wysocki <rafael.j.wysocki@intel.com>
This commit is contained in:
parent
06354d7a61
commit
e86001d6d0
@ -7,6 +7,27 @@
|
||||
* Based on step_wise.c with following Copyrights:
|
||||
* Copyright (C) 2012 Intel Corp
|
||||
* Copyright (C) 2012 Durgadoss R <durgadoss.r@intel.com>
|
||||
*
|
||||
* Regulation Logic: a two point regulation, deliver cooling state depending
|
||||
* on the previous state shown in this diagram:
|
||||
*
|
||||
* Fan: OFF ON
|
||||
*
|
||||
* |
|
||||
* |
|
||||
* trip_temp: +---->+
|
||||
* | | ^
|
||||
* | | |
|
||||
* | | Temperature
|
||||
* (trip_temp - hyst): +<----+
|
||||
* |
|
||||
* |
|
||||
* |
|
||||
*
|
||||
* * If the fan is not running and temperature exceeds trip_temp, the fan
|
||||
* gets turned on.
|
||||
* * In case the fan is running, temperature must fall below
|
||||
* (trip_temp - hyst) so that the fan gets turned off again.
|
||||
*/
|
||||
|
||||
#include <linux/thermal.h>
|
||||
@ -38,28 +59,6 @@ static void bang_bang_set_instance_target(struct thermal_instance *instance,
|
||||
* @tz: thermal_zone_device
|
||||
* @trip: the trip point
|
||||
* @crossed_up: whether or not the trip has been crossed on the way up
|
||||
*
|
||||
* Regulation Logic: a two point regulation, deliver cooling state depending
|
||||
* on the previous state shown in this diagram:
|
||||
*
|
||||
* Fan: OFF ON
|
||||
*
|
||||
* |
|
||||
* |
|
||||
* trip_temp: +---->+
|
||||
* | | ^
|
||||
* | | |
|
||||
* | | Temperature
|
||||
* (trip_temp - hyst): +<----+
|
||||
* |
|
||||
* |
|
||||
* |
|
||||
*
|
||||
* * If the fan is not running and temperature exceeds trip_temp, the fan
|
||||
* gets turned on.
|
||||
* * In case the fan is running, temperature must fall below
|
||||
* (trip_temp - hyst) so that the fan gets turned off again.
|
||||
*
|
||||
*/
|
||||
static void bang_bang_trip_crossed(struct thermal_zone_device *tz,
|
||||
const struct thermal_trip *trip,
|
||||
|